Precision filters for Coolant Distribution Units in AI and HPC data centers — built on twelve years of SS316L industrial filtration and engineered to the OCP Liquid-to-Liquid CDU guidelines. Complete coverage from FWS facility-water inlet to TCS secondary-loop protection and continuous side-stream polishing. Engineering samples and full ΔP / Beta-ratio test-data packages available now.
DOC · CDU-FILT-SOL-2026 / REV 07OCP L-L Aligned · Meta Green Cooling
12 yr
Filtration Experience
Filter maker since 2014
100 psi
Max Rated Pressure
ASME hydrostatic tested
SS316L
Wetted Material
PG & water coolants
79+
Countries Served
Industrial client base
CDU Liquid-Cooling LoopFIG 1.0
≤200 µm25–50 µm0.2–5 µm
About This Product Line
Industrial filtration, adapted to the CDU loop.
Brother Filtration has built industrial filtration since 2014 — SS316L welded housings, pleated mesh and wedge-wire elements shipped to clients in 79+ countries. We are now adapting that proven engineering to Coolant Distribution Units for AI and HPC data centers, designed to the OCP Liquid-to-Liquid CDU guidelines referenced by hyperscale operators and Meta Green Cooling. Our offering covers every filtration position in the CDU loop — from FWS facility-water inlet to TCS secondary-loop protection and continuous side-stream polishing — and ships with the test-data package CDU engineers need to qualify it.
Primary
≤ 200 µm
FWS Inlet
Secondary
25–50 µm
TCS Main Loop
Pressure
100 psi
690 kPa · System Max
Material
SS316L
Wetted Throughout
01 / 04 · FILTRATION POSITIONS
Three positions, one CDU loop.
OCP requires filtration at two positions — primary on the FWS inlet and secondary on the TCS loop — with side-stream polishing recommended as best practice. Each maps to a dedicated Brother filter, plus a commissioning flush for first-startup use.
CDU Liquid-Cooling Loop · Filtration Position Schematic
Loop schematic — flow direction shown by arrows. Primary protects the heat exchanger; secondary protects cold plates; side-stream continuously polishes 5–10% bypass flow.
01STD
FWS Side
Primary Filter
OCP Requirement · ≤ 200 µm
Brother Product · FWS Strainer
Protect the plate heat exchanger from facility-water particulates.
02CORE
TCS Side
Secondary Filter
OCP Requirement · 25 – 50 µm
Brother Product · TCS Pleated Filter
Last line of defense before coolant reaches GPU/CPU cold plates.
03OPT
TCS Bypass
Side-Stream Polishing
OCP Requirement · 0.2 – 5 µm
Brother Product · Side-Stream Polisher
Continuous 24/7 sub-micron purification on bypass flow.
02 / 04 · PRODUCT LINE
CDU filters & engineering services.
Filters for every position in the CDU loop, designed to the OCP Liquid-to-Liquid guidelines — SS316L wetted materials throughout, rated to 100 psi system pressure, and tested for compatibility with water-based and propylene-glycol coolants. Each ships with the validation data your engineering team needs to qualify it.
01
01 · Primary Filter · FWS Inlet
FWS Strainer
SS316L wedge-wire basket strainer for facility water inlet. Fully washable and reusable for 10+ year CDU service life.
SS316L pleated mesh secondary filter — the most critical position. Hot-swappable dual-housing with integrated ΔP monitoring port. Fits in-rack and in-row CDU formats.
High-dirt-holding flush filter for CDU initial startup — captures pipe debris, weld slag and construction FOD before cold plates are first exposed to coolant. Used once at commissioning, then handed over to the standard secondary filter for ongoing operation.
The data CDU engineers need to design us in — shipped with every sample. Pressure-drop (ΔP) curves, ISO 16889 Beta-ratio efficiency, ICP-MS metal-ion and TOC long-term chemistry results, so your team can cut design-in validation time and cost.
ΔP CurvesPer Flow / Coolant
EfficiencyISO 16889 Beta
ChemistryICP-MS / TOC
MaterialEN 10204 3.1 MTR
DeliveryWith Sample / 24 h
06
06 · Custom CDU Filter OEM
OEM Program
Custom dimensions, interface connections, private branding and EN 10204 3.1 material documentation packages for CDU manufacturers. Low MOQ, flexible production scheduling.
Position-by-position engineering specifications, OCP alignment and recommended ratings.
Parameter
Primary · FWS Strainer
Secondary · TCS Pleated
Side-Stream · Polisher
Position
FWS facility water inlet
TCS server-side main loop
TCS bypass · continuous
OCP requirement
≤ 200 µm (Required)
25 – 50 µm (Required)
0.2 – 5 µm (Recommended)
Filtration rating
150 / 200 / 250 µm
25 µm / 50 µm
0.2 / 1 / 5 µm
Media / material
SS316L wedge-wire
SS316L pleated mesh
PES / PVDF membrane
Max pressure
100 psi
100 psi
100 psi
Connection
Victaulic / Flanged
Tri-clamp / Victaulic
Tri-clamp · 10"/20"
Design / feature
Washable & reusable
Hot-swap + ΔP port
5–10% bypass, no extra pump
Coolant compatibility
Water · PG · EG
DI water · 25–30% PG
Water · glycol (+10–30% ΔP)
Documentation
EN 10204 3.1 + ASME
EN 10204 3.1 + ASME
EN 10204 3.1
Primary: Industry CDU standard — primary filter ≤ 200 µm protects the heat exchanger. Available in 150/200/250 µm absolute ratings to match water quality.
Secondary: Industry CDU standard — secondary filter 25–50 µm, hot-swappable, protects cold plates. 25 µm for in-rack, 50 µm for in-row.
Side-Stream: Industry best practice — 0.2–5 µm side-stream polishing for long-term coolant quality maintenance. PES membrane, 10"/20" replaceable.
04 / 04 · INDUSTRY STANDARDS
Meeting industry CDU filtration requirements.
Filters designed to the OCP Liquid-to-Liquid CDU filtration specs, ASME hydrostatic-tested and backed by EN 10204 3.1 material reports. UL, CE / PED and OCP Inspired registration are in active qualification through 2026. Compatibility tested across the full coolant stack used in modern hyperscale CDUs.
Frequently asked questions from CDU manufacturers, hyperscale operators and data-center engineers evaluating liquid-cooling filtration for AI & HPC workloads.
Updated 2026 · 8 Questions
Q01What is a CDU filter and why do liquid-cooled AI data centers need one?+
A CDU (Coolant Distribution Unit) filter keeps coolant clean as it circulates between the facility water supply (FWS) and the technology cooling system (TCS) that feeds GPU and CPU cold plates.
In AI and HPC data centers, even sub-millimeter particulates can clog the micro-channels inside cold plates and trigger thermal throttling or hardware failure. OCP Liquid-to-Liquid CDUs require filtration at two positions — primary on the FWS inlet and secondary on the TCS loop — with continuous side-stream polishing recommended as best practice.
Q02What is the difference between primary, secondary and side-stream CDU filtration?+
Primary (FWS inlet, ≤ 200 µm) — protects the plate heat exchanger from facility-water sediment and pipe debris. Washable wedge-wire basket strainer.
Secondary (TCS main loop, 25–50 µm) — last line of defense before coolant reaches the cold plates. OCP best practice requires this position to be hot-swappable.
Side-stream polishing (TCS bypass, 0.2–5 µm) — continuous 5–10% bypass with a PES / PVDF membrane, running 24/7 to remove oxidation byproducts and biological films.
Q03Why is 25–50 µm the standard rating for the secondary CDU filter?+
25–50 µm is the rating window adopted by OCP Liquid-to-Liquid and Meta Green Cooling because it provides adequate protection for cold-plate micro-channels (typically 100–300 µm wide) while keeping pressure drop manageable at the high flow rates required by AI racks.
25 µm is recommended for in-rack CDUs with denser cold plates; 50 µm is preferred for in-row CDUs where a lower ΔP is more important. Both ratings ship in Brother's hot-swap TCS pleated filter housing.
Q04What does "hot-swap" mean for a CDU filter and why is it required?+
A hot-swap CDU filter housing has dual cartridge chambers and an isolation valve that lets operators replace one cartridge while the other continues to carry full flow. The CDU never has to shut down for filter maintenance — critical for AI training jobs that cannot tolerate downtime.
OCP Liquid-to-Liquid lists hot-swap as best practice. Brother's hot-swap TCS pleated filter is built with an integrated ΔP monitoring port so the CDU controller can flag clog conditions before pressure drop affects pump head.
Q05Are Brother Filtration CDU filters compatible with propylene glycol and engineered coolants?+
Yes. All Brother CDU filters use SS316L wetted materials and are verified compatible with DI water, 25% propylene glycol (PG), 30% ethylene glycol (EG), Clariant Antifrogen and Dynalene HC.
Pressure drop for the side-stream membrane cartridges increases 10–30% when running glycol mixes versus pure water at the same flow rate — sizing curves and chemical compatibility data are provided on request.
Q06Why is SS316L the preferred wetted material for CDU filtration?+
SS316L is the industry-preferred grade for CDU wetted components because it resists pitting and crevice corrosion from glycol-based coolants, holds up to 100 psi system pressure with a 10+ year service life, and is fully traceable via EN 10204 3.1 material test reports.
Lower-grade stainless and brass fittings can shed metal ions into the coolant loop, which then deposit inside cold-plate micro-channels and increase thermal resistance over time.
Q07What certifications and documentation come with Brother Filtration CDU filters?+
Every CDU filter ships with ASME B31.1 / B31.3 hydrostatic pressure test results, EN 10204 3.1 material test reports (MTR), and ΔP curves, ISO 16889 Beta-ratio, ICP-MS and TOC test data.
Quality is ISO 9001 certified; materials are RoHS and REACH compliant. UL Listing, CE / PED and OCP Inspired registration are in active qualification through 2026. The full document package is available within 24 hours of inquiry.
Q08Do you offer OEM or private-label CDU filters for CDU manufacturers?+
Yes. The Brother OEM Program supports custom dimensions, interface connections (Victaulic, flanged, Tri-clamp, NPT or custom), private branding and EN 10204 3.1 documentation packages tailored to each CDU manufacturer.
MOQs are flexible and typical lead time for engineering samples is 4–6 weeks. White-label options and dedicated CDU production lines mean inventory programs can be set up alongside ongoing manufacturing.
Whether you're a CDU manufacturer building your next-gen product line or a data center operator evaluating filtration upgrades — our engineering team is ready with samples, datasheets, pressure-drop curves, and material documentation.
Email
sales@brotherfiltration.com
Website
www.brotherfiltration.com
Founded
2014 · 79+ countries
Response
Within 24 hours
Request a Sample or DatasheetFORM · CDU-INQ-26
SLA · < 24 H Response · Demo form — submissions display a confirmation only.
Inquiry received.
Our CDU specialist replies within 24 hours with samples, datasheets and ΔP curves.
Datasheet & ΔP curves
CDU Filtration datasheet package — ΔP curves, ISO 16889 Beta-ratio and EN 10204 3.1 material data. Enter your email and we'll send the PDF within 24 hours.
On its way.
Check your inbox for the CDU datasheet package. (Demo — no email is actually sent.)