Liquid cooling only works while the coolant stays clean. Particles from pipework, installation and wear collect in cold plate channels, quick disconnects and heat exchangers. Flow drops, pressure drop climbs and chip temperatures follow. Filtration is how data center operators and CDU makers stop that from happening.

This library collects BOLEFIL’s engineering guides on filtration for liquid-cooled data centers: where filters go, how to choose a micron rating, how to size for pressure drop, and how to keep a closed loop clean over years of service.

Where filtration sits in a liquid cooling system

A liquid-cooled data center usually runs three connected water loops, and each one needs its own filtration.

  • Facility water system (FWS). Treated water runs from the chiller plant to the CDU heat exchanger. A strainer at the CDU inlet catches pipe scale, rust and installation debris before they reach the heat exchanger. BOLEFIL’s FWS strainer is a washable SS316L wedge-wire basket rated 150 to 250 µm.
  • Technology cooling system (TCS). This is the closed loop inside the CDU and the racks, usually water or PG25 coolant, and the most sensitive part of the system. An inline filter, most often 25 or 50 µm, protects cold plates and quick disconnects. A side-stream filter treats a small share of the flow to a much finer rating and removes the fine particles that build up over time.
  • Condenser water and make-up water. Open cooling towers pick up dust and debris from the air, and make-up water brings in suspended solids. Bag filter housings, high flow housings and side-stream filters keep these upstream loops clean, so less reaches the CDU.

One more filter is used only once: a high-capacity flush filter at commissioning. It catches weld slag and construction debris before the cold plates first see coolant.

What the industry guidance says

The Open Compute Project’s guidelines for PG25 coolant (Revision 2.0, September 2026) describe the same layout:

  • Most CDUs contain 25 or 50 µm inline filters that work in tandem with side-stream filters.
  • Side-stream filtration takes a small proportion of the flow, typically 5 to 15 percent, and is strongly recommended for systems above 250 gallons of fluid.
  • For full-flow filters, OCP recommends duplex housings, so elements can be cleaned or replaced without a shutdown.
  • It prefers 304L or 316L stainless steel for wetted parts.
  • It warns that overly fine filtration may remove some antifoam additives from the fluid.

Our guides follow this guidance and link to it where it applies.

How to use this library

  • New to liquid cooling filtration? Start with the guide to flow, contamination and pressure drop. Then read the guide to filter positions and micron ratings.
  • Choosing a filter for a CDU? Go to the micron rating, pressure drop and full-flow versus side-stream guides.
  • Running a system already? The guides on closed-loop contamination and cold plate fouling explain where particles come from and how to spot them in flow and pressure data.

01. Liquid Cooling Systems

02. CDU Filtration

03. Filter Selection

04. Filtration Solutions

05. Contamination Control

Frequently asked questions

What micron rating do CDU filters use?

Most CDU loops use 25 or 50 µm inline filters on the technology cooling system (TCS) side, often called the secondary filter. The Open Compute Project’s PG25 guidelines (Rev 2.0, September 2026) describe the same range, with finer side-stream filters working alongside. Always check the CDU and cold plate maker’s specification first.

Where do filters sit in a CDU loop?

In three places: a strainer on the facility water (FWS) inlet protects the CDU’s heat exchanger from scale and debris; an inline filter on the TCS loop protects cold plates and quick disconnects; and a side-stream filter polishes a small share of the flow to a finer rating. A separate flush filter is used once, at commissioning, to catch construction debris before the cold plates see coolant.

Full-flow or side-stream filtration: which do I need?

Most systems use both. A full-flow filter sits in the main path, so all the coolant passes through it, but its pressure loss adds to the pump load. A side-stream filter treats part of the flow in a bypass loop, to a finer rating. OCP’s PG25 guidelines strongly recommend side-stream filtration for systems above 250 gallons of fluid, and duplex housings for full-flow filters, so elements can be changed without a shutdown.

How do I size a CDU filter for pressure drop?

Size on the loaded pressure drop, not only the clean value on the datasheet. As the element collects particles, its pressure drop rises and takes pump head from the rest of the loop. Set a terminal differential pressure for changing the element, compare data for the complete filter assembly, not the element alone, and use the filter’s ΔP reading to monitor the loop.

Why do closed TCS loops still collect particles?

“Closed” describes the coolant path, not its cleanliness. Particles enter during manufacturing, installation, commissioning, filling and maintenance, and components can also generate particles over time. These particles circulate and settle at filters and in narrow passages such as cold plate channels. That is why a closed loop still needs filtration, and a flush at commissioning.

Which stainless steel is used for wetted parts with PG25 coolant?

OCP’s PG25 guidelines list 304L, 316L or higher stainless grades as preferred for wetted parts. Ask us which grade suits your coolant and treatment chemicals.